Modbus RTU filter fields ​

The filter operates on parsed Modbus messages. Field names start with modbus.. The syntax is shared with other profiles, but trace.* and can.* fields are not available in this catalog.

Catalog ​

Address, function and result ​

FieldTypeMeaning and applicability
modbus.unitIdIntegerRTU device address in a valid record; 0 is used for a broadcast request
modbus.functionIntegerFunction code without the exception bit. A 0x83 response belongs to function 0x03
modbus.requestBooleanRequest, when the role is known; includes broadcast requests
modbus.responseBooleanResponse, when the role is known
modbus.broadcastBooleanValid RTU broadcast request to address 0
modbus.exceptionBooleanValid exception response
modbus.exceptionCodeIntegerException code; absent in normal responses and requests
modbus.validBooleanThe record passed structure and CRC validation; false selects invalid records

Most parsed fields are absent in an invalid message. Therefore, modbus.valid == false and modbus.unitId == 7 cannot find every damaged message believed to belong to that device: the address may be unreliable and unavailable to the filter.

Request or response roles are not determined by RX/TX alone. In particular, identical single-item write messages cannot always be classified unambiguously during passive observation.

Range and data ​

FieldTypeMeaning and applicability
modbus.startAddressIntegerZero-based starting or target address, when included in the PDU
modbus.quantityIntegerRequested or acknowledged item count, when included in the PDU
modbus.byteCountIntegerDeclared data byte count, when included in the PDU
modbus.dataBytesFunction data without the device address, function code, starting address, quantity, byte count or CRC; see the table below

Shared Modbus model fields ​

These fields remain in the catalog, but address and function are sufficient for typical RTU traffic filtering.

FieldTypeMeaning and applicability
modbus.transportStringrtu in this profile. The shared catalog also recognizes tcp, which is outside this section
modbus.transactionIdIntegerShared catalog field for Modbus TCP. Always absent in RTU

Where to find ranges and data ​

FunctionsRequestNormal response
01, 02, 03, 04 — readstartAddress, quantity; no databyteCount, data; no startAddress or quantity
05, 06 — write one itemstartAddress, two value bytes in data; no quantityThe same fields
0F, 10 — write multiple itemsstartAddress, quantity, byteCount, datastartAddress, quantity; no data
Exception response—exceptionCode; no normal response range or data

modbus.data[0] is the first function data byte, not the first RTU frame byte. In a register read response, it is the high byte of the first register. The device documentation defines the meaning and conversion of its value.

Examples ​

Holding register reads for address 7, including exception responses:

text
modbus.unitId == 7 and modbus.function == 0x03

A request to read ten registers starting at address 100:

text
modbus.unitId == 7 and modbus.request == true and modbus.function == 0x03 and modbus.startAddress == 100 and modbus.quantity == 10

This selects requests. A read response does not contain address 100 and is not automatically joined to the request.

Exception responses:

text
modbus.exception == true

Responses with exception code 0x02:

text
modbus.exceptionCode == 0x02

Invalid records:

text
modbus.valid == false

Broadcast requests:

text
modbus.broadcast == true

Recognized write requests:

text
modbus.request == true and modbus.function in (0x05, 0x06, 0x0F, 0x10)

Read responses with 0x1234 in the first register:

text
modbus.function == 0x03 and modbus.response == true and modbus.data[0] == 0x12 and modbus.data[1] == 0x34

The starting address in an expression is a protocol address. Do not enter labels such as 40001 without converting them according to the device documentation.

For more on matching messages, see analyzing Modbus RTU traffic.

Protohaund is independent software and is not affiliated with, endorsed by, sponsored by, or certified by any third-party organization referenced in the application.Third-party names, trademarks, product names, device names, protocol names, and standards are referenced solely to identify vehicle applicability, supported products, technologies, protocols, formats, or compatibility.All third-party trademarks and other marks are the property of their respective owners. Their use does not imply any affiliation with, endorsement of, certification of, or approval of Protohaund by their respective owners.Compatibility is limited to the features, devices, protocols, standards, and versions explicitly documented by Protohaund.